Inverter Sizing Calculator

Pick an inverter kW rating from your running load, margin and surge

Updated July 12, 2026 · Live

What this tool does

Sizes an off-grid or backup inverter in kW from your continuous running load and a safety margin, and checks your peak surge load against it.

Enter the continuous load, the peak surge and a safety margin; the calculator recommends the nearest standard inverter size and checks the surge.

Inputs
W
W
%
Result

Recommended Inverter

3.0 kW

Continuous Load + Margin
2.50 kW
Safety Margin
25%
Peak Surge to Cover
4.00 kW
Surge Check
At a typical 2× surge rating a 3.0 kW inverter covers 6.0 kW, so this surge is covered. Check the datasheet
Note
Confirm the inverter surge rating exceeds your largest motor start-up
Plain Estimate
From BrightScale Labs
Invoice maker
Quote at the door. Signed on the spot.
Estimates and invoices for trades, built while you are still in the room.
Scan to get
Get it onGoogle Play

People also use

Formula Used
Pinv=Lcont⋅(1+m)1000P_{inv} = \dfrac{L_{cont}\cdot (1+m)}{1000}
LcontL_{cont}
Continuous load (W)
mm
Safety margin fraction (percentage ÷ 100)
PinvP_{inv}
Sized inverter power (kW), rounded up to a standard rating

How the inverter sizing works

An inverter turns the battery or solar DC into the AC that your appliances use, and it has to carry everything that runs at once. This calculator takes the continuous load, adds a safety margin and rounds up to the nearest standard inverter size. The formula is P = L × (1 + m) ÷ 1,000, where L is the continuous load in watts and m the margin as a decimal. The surge figure is then compared against what that inverter can briefly deliver.

Example with the defaults: a 2,000 W continuous load with a 25% margin is 2,000 × 1.25 = 2,500 W, or 2.5 kW. The next standard size up is 3.0 kW. The 4,000 W surge is covered if the inverter can deliver twice its rating for a few seconds, because 3.0 × 2 = 6.0 kW. A 25% margin keeps the load at 80% of the rating, since 1 ÷ 1.25 = 0.8.

A well pump changes the answer. With 1,500 W running and a 6,000 W start-up surge, the load plus 25% is 1,875 W, which rounds up to 2.0 kW. But 2.0 kW at twice its rating covers only 4.0 kW of surge, so the surge needs an inverter of about 6,000 ÷ 2 = 3.0 kW or more, or one with a higher surge rating. The tool shows that in the surge check row. The inputs are in watts, so the US and metric versions give the same result.

What you enter

Three numbers drive the result. The continuous load is the total running power of everything that will be on at the same time. Add up the nameplate watts of each appliance, and count only what runs together. The peak surge is the brief start-up power of the largest motor, such as a well pump, fridge compressor or power tool. A motor can draw several times its running power for a second or two. The safety margin is the headroom above the continuous load.

Enter the surge from the appliance's nameplate or manual and not from a guess. The tool refuses a blank or zero continuous load and a margin outside 0 to 100%, and a surge of 0 is accepted when there are no motor loads.

Reading the result

The recommended size is the smallest standard rating that covers the load plus margin: 0.6, 1, 1.5, 2, 2.4, 3, 3.6, 4.6, 5, 6, 8, 10, 12 or 15 kW, then whole kW above that. Real inverters come in their own ratings, so treat it as a target and choose the nearest model at or above it. Inverter ratings may be in W or VA. Motors and other inductive loads draw more VA than watts, so check which one a rating uses.

The surge check compares your peak with a typical 2× surge rating. That is a common specification and not a universal one, so read the datasheet, which lists continuous power, surge power and the duration of the surge. An inverter can also derate in a hot room, so give it ventilation and do not size it to the last watt.

Safe by design

This calculator does the arithmetic of sizing. It deliberately stops at the line a certified installer must sign off. It will never tell you a cable or fuse size, an earthing arrangement, a battery charge voltage or a roof structural load, because those are regulated calculations where a wrong number causes fire, electrocution or collapse. All electrical work must be carried out by a qualified, certified installer, and this page is not an installation guide.

Assumptions and limits

This method sizes an inverter from the load, which suits off-grid and backup systems. A grid-connected solar inverter is sized from the solar array instead, usually with an array DC rating a little above the inverter's AC rating, and the grid operator's rules limit its size. In the United States, NEC Articles 690 and 705 cover solar PV systems, and UL 1741 covers inverter equipment, and local inspectors apply them. An inverter that is far larger than the load wastes energy at light load, because its own consumption and its efficiency at low power both count against it, so do not oversize without reason.

The tool does not model the battery voltage, inverter efficiency, derating in heat or the power factor of your loads. Add the loads you actually use, check the datasheet of the model you choose and ask a qualified installer to confirm the design before you buy.

Using it with the rest of BuildMetricLab

Pair this estimate with the battery bank, solar array and charge controller calculators to size the rest of an off-grid system. Every BuildMetricLab tool runs entirely in your browser, with no sign-up. Nothing you type is sent to a server, and the formula is shown on the page so the maths can be audited.

Sources & methodology

The recommended size is continuous load × (1 + margin ÷ 100) ÷ 1,000 in kW, rounded up to the next standard rating in the list 0.6, 1, 1.5, 2, 2.4, 3, 3.6, 4.6, 5, 6, 8, 10, 12 and 15 kW, and above 15 kW to the next whole kW. A 25% margin means the load is 80% of the rating. The surge row compares your peak surge with a typical 2× surge rating, which is a common but not universal specification: the inverter datasheet is the authority. The continuous load must be above zero, the surge zero or more, and the margin between 0 and 100%. Inputs are in watts, so both unit systems agree. The method suits off-grid and backup inverters sized from the load. It does not size a grid-connected inverter, which follows the solar array's DC rating and the grid operator's rules, and it does not model battery voltage, power factor, derating for heat or inverter efficiency.

Frequently asked questions

What is the difference between continuous and surge?

Continuous is the steady load the inverter can carry indefinitely. Surge is the brief spike when a motor or compressor starts, often several times its running power for a second or two. Inverters quote both ratings, and both must cover your load. Many are rated for about twice their continuous output for a few seconds, but the datasheet figure is the one that counts.

What safety margin is sensible?

A margin of 20 to 30% above the continuous load is a common planning figure. A 25% margin keeps the load at about 80% of the rating, because 1 ÷ 1.25 = 0.8. It leaves room for extra appliances and avoids running the inverter flat out, and inverters can also derate in heat. Larger margins add cost.

Why round to a standard size?

Inverters are sold in fixed ratings, so the tool picks the smallest standard rating that meets your load plus margin: 0.6, 1, 1.5, 2, 2.4, 3, 3.6, 4.6, 5, 6, 8, 10, 12 or 15 kW, then whole kW above that. It is a target, and real models differ, so choose the nearest model at or above it.

Does a bigger inverter waste energy?

Somewhat. Every inverter draws some power just to stay on, and its efficiency is lowest at very light load, so a heavily oversized inverter can waste more energy when your load is small. Matching the size to your load plus a sensible margin keeps standby losses down, and the datasheet shows the idle draw.